Fire

CO2 Extinguishers

Areas Of Use

These extinguishers are not ideal for outdoor use and not suitable to extinguish a deep-seated fire. They are ideal for indoor applications in areas where technical equipment such as computers, cash sale points, DB's and electrical appliances are situated as a first means of attack. CO2 gas extinguishes the fire by removing the available oxygen and cooling down the fire, leaving no residue (mess).

Certification Mark

SANS 1567.

Construction

High-pressure seamless aluminium cylinder, robustly constructed to international standards. Lever operated brass head, with built in pressure release safety disc, to rupture at 20 000 kPa.
Cylinder conforms to BS 5045/3/C/S.

Sizes

- 2kg Swivel Horn
- 5kg with discharge hose and horn

Features

Completely controllable for extended use; Inexpensive to recharge; very simple operation;
discharge horn and instruction label colour coded black; corrosion resistant.

Maintenance

Every 12 months, or sooner (depending on local authorities). Hydrostatic pressure testing of cylinder is required every 10 years to comply with SANAS.